DLF360 Earth Leakage Circuit
Breaker |
| |
Application: |
| |
The item is in
accordance with standards of VDE 0664, CEE27 and BS4293
etc., applying to the circuit of AC 50/60Hz, 240V single
phase, 415V three phases and below it for industrial and
mining enterprise, building trade, commerce and family.
To mainly prevent electric fire and personal casuatly accident
caused by personal electric shock or leakage of electrified
wire netting, this ELCB is a current-operated, fast leakage
protector of pure electromagnetic type, which can break
off fault circuit rapidly in order to avoid occurrence of
accident. The item is precise in structure, less elements,
without auxiliary power and high working reliability. The
function of the switch won be influenced by ambient temperature
and lighting.The mutual inductor of the item is used to
test vector differential value of passing current, and produces
are levant output power and add it differential value of
protected circuit of personal electric shock is up to or
over leakage operating current, the tripper will act and
cut off so that the item will take effect of protection. |
| |
|
| |
|
|
|
|
| |
TECHNICAL DATA: |
| |
| Tripping
time:100ms(depending on specifications 5XI N400ms) |
| Ambient temperature:
-5°C~+55°C |
| Climatic resistance:
55°C/28 cycles |
| Vibration resistance:
Minimun 5g 30min, 0~8Hz |
| Life expectance:At
least 10,000 operations |
|
| |
Technical Specification: |
| |
| Type |
Rated
current |
Leakage
acting current |
Range
of break-off |
Rated
voltage |
| F362 |
16A 25A 32A
40A 63A |
10mA 30mA 100mA
300mA |
0.5~1.0XI N |
240V(220V) |
| F364 |
25A 32A 40A 63A |
30mA 100mA 300mA |
0.5~1.0XI N |
240V/415V
(220V/380V) |
|
|
|
|
|
|
|
|
|
|
|
Dimension And Mounting
Notice
1. Leakage Protection function of RCCB is tested and adjusted
by the manufacturer, users can not open the product at random
during usage.
2. After using RCCB for a certain time (normally one month),
test button should be pressed once in a state of making the circuit
to check whether the function of RCCB is normal and reliable (press
test button once, the RCCB can break off once). If abnormal, it
should be unloaded and sent to the manufacturer for repair.
3.RCCB must not be wetted or soaked by rain, snow or water during
the course of transportation, storation and usage.
4.RCCB can not play the role of protection when short circuit
occurs.
|
|